CAIDI

Reliability index used by electric power utilities

The Customer Average Interruption Duration Index (CAIDI) is a reliability index commonly used by electric power utilities.[1] It is related to SAIDI and SAIFI, and is calculated as

CAIDI = U i N i λ i N i {\displaystyle {\mbox{CAIDI}}={\frac {\sum {U_{i}N_{i}}}{\sum {\lambda _{i}N_{i}}}}}

where λ i {\displaystyle \lambda _{i}} is the failure rate, N i {\displaystyle N_{i}} is the number of customers, and U i {\displaystyle U_{i}} is the annual outage time for location i {\displaystyle i} . In other words,

CAIDI = sum of all customer interruption durations total number of customer interruptions = SAIDI SAIFI {\displaystyle {\mbox{CAIDI}}={\frac {\mbox{sum of all customer interruption durations}}{\mbox{total number of customer interruptions}}}={\frac {\mbox{SAIDI}}{\mbox{SAIFI}}}}

CAIDI gives the average outage duration that any given customer would experience. CAIDI can also be viewed as the average restoration time.

CAIDI is measured in units of time, often minutes or hours. It is usually measured over the course of a year, and according to IEEE Standard 1366-1998 the median value for North American utilities is approximately 1.36 hours.

References

  1. ^ Yeddanapudi, Sree. "Distribution System Reliability Evaluation". Iowa State University. Archived from the original on 26 December 2011. Retrieved 18 June 2011.
  • v
  • t
  • e
Reliability indices
Generic
Electricity distribution
  • ASUI
  • ASAI
  • CAIDI/SAIDI
  • CAIFI/SAIFI
  • MAIFI
  • CTAIDI
Electricity generation